Case 1: Single-phase 200 V / 20 A / 30 m / Cu 25 mm²
Input
Circuit=single, V=200 V, I=20 A, L=30 m, material=Cu, temp=60 °C, pf=1.0, standard=IEC, size=25 mm², allowable=3.0%
Output
ΔV=0.96V, ΔV%=0.48%, Pass
Calculate voltage drop (V and %) from voltage, current, distance, and conductor conditions.
The allowable threshold is a reference Pass/Warn comparison only. Select a standard set to see cable-size candidates ranked by voltage drop.
Input
Circuit=single, V=200 V, I=20 A, L=30 m, material=Cu, temp=60 °C, pf=1.0, standard=IEC, size=25 mm², allowable=3.0%
Output
ΔV=0.96V, ΔV%=0.48%, Pass
Input
Circuit=three-phase, V=400 V, I=80 A, L=80 m, material=Al, temp=60 °C, pf=0.9, standard=IEC, size=16 mm², allowable=3.0%
Output
ΔV=20.40V, ΔV%=5.10%, Warn
No. Enter one-way distance. Internally, single-phase uses round-trip (2L), while three-phase uses one-way distance with the √3 formula.
No. Pass/Warn is only a reference comparison. Always prioritize regulations, internal standards, design documents, and manufacturer data.
Use manual input when you have resistance values from the manufacturer or a design sheet. Presets are approximations based on conductor cross-sectional area.
In this quick model, the resistive drop is multiplied by cosφ. Reactance is not included.