Case 1: Single-phase 200V / 20A / 30m / Cu 25mm2
Input
Circuit=single, V=200, I=20, L=30, material=Cu, temp=60, pf=1.0, standard=IEC, size=25, allowable=3.0%
Output
ΔV=0.96V, ΔV%=0.48%, Pass
Calculate voltage drop (V / %) from voltage, current, distance, and conductor conditions.
The allowable threshold is shown as reference Pass/Warn only. When a standard set is selected, cable candidates are listed from the voltage-drop perspective.
Input
Circuit=single, V=200, I=20, L=30, material=Cu, temp=60, pf=1.0, standard=IEC, size=25, allowable=3.0%
Output
ΔV=0.96V, ΔV%=0.48%, Pass
Input
Circuit=three-phase, V=400, I=80, L=80, material=Al, temp=60, pf=0.9, standard=IEC, size=16, allowable=3.0%
Output
ΔV=20.40V, ΔV%=5.10%, Warn
No. Enter one-way distance. Internally, single-phase uses round-trip (2L) and three-phase uses one-way (sqrt(3) formula).
No. Pass/Warn is a reference comparison only. Always prioritize regulations, internal standards, design documents, and manufacturer data.
Use manual input when you have manufacturer or design-sheet resistance values. Preset values are area-based approximations.
In this quick model, the resistive drop is adjusted by cosphi. Reactance is not included.